| Electrical |
| Power
Requirement |
100-140
or 220-260 VAC, 10 W |
| Mounting |
4 or
6 Jaw Meter Socket
Pole
Brackets
Internal
block electrical connections for pole mounted units
Optional
Amphenol connector for pole mounted units |
| Output
contactor |
30 A,
120/240 VAC
15 second
On duration for MOTOR OP switches
100 millisecond
On duration for SOLENOID switches |
| Fuse |
15 A
Slo-Blo |
| Surge/Lightning Protection |
ANSI
C37.90.1-1989 |
| Voltage
Accuracy |
±0.5
VAC, 0.1 VAC resolution |
| Temperature
Accuracy |
±1° F,
1° F resolution |
| Current
Accuracy |
±1% sensor
accuracy, 0.5 A resolution.
Compatible
sensors: Lindsey CVMI and Fisher-Pierce 1301 |
| Phase
Angle Accuracy |
±1º
lead or lag |
| Time
Accuracy |
Line
synchronized and Quartz crystal controlled on battery backup,
±0.001% |
| Battery |
Lithium
cell, 10 year life, size - 2/3 A |
| Display |
Liquid
crystal, backlit |
| Computer
Interface |
RS-232
DB-9
female on front panel
2400
baud, 3-5 min. to download 5,000 data points |
|
Mechanical
|
| Mounting |
Meter
socket, 4 or 6 jaw ringed or ringless
Pole
brackets |
| Enclosures |
Meter
socket |
| |
NEMA
4X weather-tight fiberglass
8.75"
x 10.75" x 5.5"
7.2 lbs. |
| |
Pole
mount |
| |
Weather-tight
fiberglass
10.75"
x 12.75" x 5.6"
7.9 lbs. |
|
Environmental
|
| Temperature |
-30º
to +85º C |
| Humidity |
5 - 95
% non-condensing |
|
Settings
|
| Voltage |
Open:108
- 130 / 213 - 260 VAC; Minimum: Close Volts +3 VAC
Close:
105 - 127 / 210 - 257 VAC; Maximum: Open Volts -3 VAC
5 minute
time-averaged voltage response
Settings
0.1 volt increments |
| Temperature |
Open:
0° - 120° F; No closer than ±5° F to Close temperature
Close:
0° - 120° F; No closer than ±5° F to Open temperature
° C display
optional
30 minute
time-averaged temperature response
Settings
in 1° F increments |
| Amps
Reactive |
Open:
100 A Leading - 598 A Lagging;
Maximum: Close Amps - 2 A
Close:
0.5 A Leading - 600 A Lagging;
Minimum:
pen Amps + 2 A
5 minute
time-averaged current response
Settings
in 0.5 A increments |
| Time Delay |
3 - 600 seconds Settings in 3 second increments |
| Max Operations/Day |
Configurable from 2-24 |
| Manual
Trip |
Center
off
Momentary
Open or Close
Close
and Open operations delayed by selected Time Delay
5 Minute
delay following Open before re-close |
| Neutral
Amps Trip |
3 - 60
A, harmonic filtered
5 minute
time-averaged response
5 minute
minimum trip time |
| PT
Ratio Set |
1 - 300 |