Series 1000/2000 Specifications

Electrical
Power Requirement 100-140 or 220-260 VAC, 10 W
Mounting 4 or 6 Jaw Meter Socket
Pole Brackets
Internal block electrical connections for pole mounted units
Optional Amphenol connector for pole mounted units
Output contactor 30 A, 120/240 VAC
15 second On duration for MOTOR OP switches
100 millisecond On duration for SOLENOID switches
Fuse 15 A Slo-Blo
Surge/Lightning Protection ANSI C37.90.1-1989
Voltage Accuracy ±0.5 VAC, 0.1 VAC resolution
Temperature Accuracy ±1° F, 1° F resolution
Current Accuracy ±1% sensor accuracy, 0.5 A resolution.
Compatible sensors: Lindsey CVMI and Fisher-Pierce 1301
Phase Angle Accuracy ±1º lead or lag
Time Accuracy Line synchronized and Quartz crystal controlled on battery backup, ±0.001%
Battery Lithium cell, 10 year life, size - 2/3 A
Display Liquid crystal, backlit
Computer Interface RS-232
DB-9 female on front panel
2400 baud, 3-5 min. to download 5,000 data points

Mechanical

Mounting Meter socket, 4 or 6 jaw ringed or ringless
Pole brackets
Enclosures Meter socket
  NEMA 4X weather-tight fiberglass
8.75" x 10.75" x 5.5"
7.2 lbs.
  Pole mount
  Weather-tight fiberglass
10.75" x 12.75" x 5.6"
7.9 lbs.

Environmental

Temperature -30º to +85º C
Humidity 5 - 95 % non-condensing

Settings

Voltage Open:108 - 130 / 213 - 260 VAC; Minimum: Close Volts +3 VAC
Close: 105 - 127 / 210 - 257 VAC; Maximum: Open Volts -3 VAC
5 minute time-averaged voltage response
Settings 0.1 volt increments
Temperature Open: 0° - 120° F; No closer than ±5° F to Close temperature
Close: 0° - 120° F; No closer than ±5° F to Open temperature
° C display optional
30 minute time-averaged temperature response
Settings in 1° F increments
Amps Reactive Open: 100 A Leading - 598 A Lagging;
Maximum: Close Amps - 2 A
Close: 0.5 A Leading - 600 A Lagging;
Minimum: pen Amps + 2 A
5 minute time-averaged current response
Settings in 0.5 A increments
Time Delay 3 - 600 seconds
Settings in 3 second increments
Max Operations/Day Configurable from 2-24
Manual Trip Center off
Momentary Open or Close
Close and Open operations delayed by selected Time Delay
5 Minute delay following Open before re-close
Neutral Amps Trip 3 - 60 A, harmonic filtered
5 minute time-averaged response
5 minute minimum trip time
PT Ratio Set 1 - 300

 